RIEVTECH — RIEVTECH STUDIO SOFTWARE MANUAL(2.0 Version).docx

RIEVTECH STUDIO SOFTWARE MANUAL The option "Buzzer" is selected by default. If it is selected, the internal buzzer of the HMI will ring when the trigger condition is satisfied. The “ Buzzer Time ” is used to set the time of buzzer ringing. It is 1 second by default. The max value of the “ Buzzer Time ” is 100 seconds. When the “ Buzzer Time ” is set “ 0 ” , the buzzer will continue ringing until the trigger condition is not satisfied. l Use Audio If the option “ Use Audio ” is selected, you can select anaudio from the "Audio Library". When the "Trigger condition" is satisfied, the audio will be played. l Trigger Address The “ Trigger Address ” can be a word or bit register.

It depends on the setting of the "Trigger Condition". l Trigger Condition You can select “ Bit ” , “ Word ” or “ Condition ” for the “ Trigger Condition ” . If you select “ Bit ” or “ Word ” , the condition is determined by the register which is given in the “ Trigger Address ” . If you select “ Condition ” , the condition needs to be given by the logic control editor box. The detailed of “ Condition ” setting is referred to: Detailed manual/ General functions/ Drawing/ Logical Control . 4.10.2.9.6 Force Buzzer off You can specify a bit register to force the buzzer off by using the control type of “ Force Buzzer off ” .

When the state of the buzzer is ON, it will be forced to OFF ifthe specified bit register is ON. 435