Smart IP43 Charger To access the expert mode settings: 1. Open the Advanced setting page and enable User defined configuration - see the 'Advanced configuration > Advanced settings' section for instructions. 2. Toggle the Expert mod e switch on to enable additional Expert mode settings (extension of the Advanced settings menu). 3. Read the warning message and then select OK to proceed. 4. The Expert mode settings (extension of the Advanced settings menu) will now be accessible. The ADDITIONAL expert mode settings include: A. Charge voltage i. BatterySafe The BatterySafe setting allows the BatterySafe voltage control to be enabled or disabled.
When BatterySafe is enabled, the rate of battery voltage increase during bulk stage is automatically restricted to a safe level. In cases where the battery voltage would otherwise increase at a faster rate, the charge current is reduced to prevent excessive gassing. B. Bulk i. Bulk time limit The bulk time limit setting restricts the maximum time the charger can spend in bulk stage as a protection measure, since the absorption voltage should have been achieved by this time. If the bulk time limit is satisfied the charger will move directly to float stage. ii.
Re-bulk voltage offset The re-bulk voltage offset setting is used to determine the re-bulk voltage threshold that will trigger a new charge cycle; the offset is relative to the configured Storage voltage (re-bulk voltage = storage voltage - re-bulk voltage offset). If the battery voltage falls below re-bulk voltage threshold while the charger is in float or storage stage and remains below it for one minute, the charger will move back into bulk charge stage. Page 58 Advanced Configuration