Smart IP43 Charger Manufacturer IP43 — 8.3. Power supply mode

Smart IP43 Charger 8.3. Power supply mode The Smart IP43 Charger range is also suitable for use as a DC power supply, to directly power loads with or without a battery connected. When the charger is used specifically as a DC power supply it is recommended to activate Power supply mode, which will disable the internal charge logic and provide a constant (configurable) DC voltage to the loads. To enable power supply mode: 1. Connect the Smart IP43 Charger AC power cable to a mains power outlet; after a short delay all LEDs will illuminate briefly, then the LEDs indicating the current charge mode and charge state will illuminate. 2.

Using a Bluetooth enabled device (mobile phone or tablet), open the VictronConnect app and locate the Smart IP43 Charger in the Device list Local page, then connect to the device (the default PIN code is stated on a label located on the side of the charger, or try 000000 if there is no label). 3. Select the Settings icon (gear in the top right corner) to access the Settings page. 4. Select the Charger in the Function filed to open the Function pop-up dialog box. 5. Select Power supply from the Function pop-up dialog box, then select OK . 6. After a short delay the BULK, ABS, FLOAT and STORAGE LEDs will be illuminated to indicate the charger function has changed to Power supply mode. 7.

If required, adjust the desired output voltage and/or the maximum current limit. 8. Power supply mode has now been enabled and configured. Page 60 Advanced Configuration