SPRUT — ANALYSIS AND DESIGN OF FLAT SLABS USING VARIOUS CODES

Numerical example: Longer span = 6.6 m Shorter span = 5.6 m Live load =7.75 kN/m 2 Assume grade of concrete as C20/25 i.e f ck = 20 MPa Where C20/25 the cylinder strength as 25 MPa, whereas C20/25 the cube strength as 20 MPa, Depth of the slab from deflection criteria = span/21 (this is based on longer span) Effective depth = 314 mm This depth also satisfies the fire resistance accordind to euro code(REI 120). Total depth = 314+15 = 350 mm(Based on the axis distance from code) D = 350 mm Load calculations Dead load acting on the slab = 0.35 x 25 = 8.75 2 / KN m = d w Live load on slab = 7.75 2 / KN m = l w The design live load shall not exceed 1.25 times the design dead load. Check:

wl/wd = 0.0885 Total design load = 2 15.45 KN/m d l w w Values of secant modulus of elasticity for C20/25 = 29 KN/mm 2 Moments calculations For longer span Calculate M = 503.118 KN-m From this calculate K, K= M/bd 2 f ck = 0.0129 K 0.60 0.182 2 0.21 where ≤ 1.0 (ok ) safe No compression reinforcement required = 0.1975 Calculation of Z Z=d /2[1-3.53K] = 298 ≤ 0.95 OK (safe) Punching shear calculations For internal columns take β= 1.15 vEd,max = β VEd /(ui deff) 37