SPRUT — ANALYSIS AND DESIGN OF FLAT SLABS USING VARIOUS CODES

Design of flat slabs using ACI-318: Drop of flat slabs: Where a drop panel is used to reduce amount of negative moment reinforcement over the column of a flat slab, size of drop panel shall be in accordance with the following: Drop panel shall extend in each direction from centerline of support a di stance not less than one-sixth the span length measured from center -to center of supports in that direction. Projection of drop panel below the slab shall be at least one -quarter the slab thickness beyond the drop.

In computing required slab reinforcement, thickness of drop panel below the slab shall not be assumed greater than one-quarter the distance from edge of drop panel to edge of column or column capital. Thickness of the slab : For slabs without interior beams spanning between the supports an d having a ratio of long to short span not greater than 2, the minimum thickness shall be in accordance with the provisions of Table below and shall not be less than the following values: (a) Slabs without drop panels as ......................... 5 in. (b) Slabs with drop panels as defined.................. 4 in. MINIMUM THICKNESS OF SLABS WITHOUT INTERIOR BEAMS 40