In an end span, total factored static moment 0 M shall be distributed as follows: Negative moment sections shall be designed to resist the larger of the two interior negative factored moments determined for spans framing into a common support unless an a nalysis is made to distribute the unbalanced moment in accordance with stiff nesses of adjoining elements. Edge beams or edges of slab shall be proportioned to resist in torsion their share of exterior negative factored moments Factored moments in middle strips: That portion of negative and positive factored moments not resisted by column strips shall be proportionately assigned to corresponding half middle strips.
Each middle strip shall be proportioned to resist the sum of the moments assigned to its two half middle strips. A middle strip adjacent to and parallel with an edge supported by a wall shall be proportioned to resist twice the moment assigned to the half middle strip corresponding to the first row of interior supports. 42