Reinforcement Depth=6 ft,Width=16.76 ft Minimum area of steel required = 0.0018 x gross area of concrete (for control of temperature & shrinkage cracking) 2 2.17 0.0018 6 16.76= 0.1808 in 12 = In 14.22 ft direction, 0 .1 8 0 8 0 .0 0 2 1 1 6 1 4 .2 2 m i n In 16.76 ft direction, m in 0.1808 0.0017 6 16.76 M M M f R f f bd b b u u u y ! 2 2 1 0.588 psi or R 0.90 6 324 c Calculation of area of steel: Along shorter span: For negative moment in column strip: 3 72.18 10 R 150.933 324 14.76 32.4 u M b Reinforcement ratio = 0.0040 Area of reinforcement = 0.0040 x 14.76 x 6 x 12 = 4.250 2 / in ft Provide Bar No.10, at a spacing of 3.5 in, 7 i n number For positive moment in column strip :
3 31.135 10 R 65 324 14.76 32.4 u M b Reinforcement ratio = 0.0017 Area of reinforcement = 0.0017x 14.76 x 6 x 12 = 1.8066 2 / in ft Provide Bar No. 8, at a spacing of 5 in, 4 in number 48