Supermicro SuperServer 1019P-WTR — Installing the Outer Rails onto the Rack

SuperServer 1019P-WTR User's Manual Chapter 2: Server Installation 2.3 Installing the Rails Warning: do not pick up the server with the front handles. They are designed to pull the system from a rack only. This section provides information on installing the chassis into a rack unit with the rails provided. There are a variety of rack units on the market, which may mean that the assembly procedure differs slightly. You should also refer to the installation instructions that came with the rack unit you are using. Installing the Outer Rails onto the Rack Each end of the assembled outer rail includes a bracket with square pegs to fit into your rack holes.

If you have an older rack with round holes, these brackets must be removed, and you must use screws to secure the rail to the rack. These rails fit a rack between 26" and 33.5" deep. Identifying the Sections of the Rack Rails Outer Rail Installation 1. Align the square pegs on the front end of the rail with the square holes on the front of the rack (C). Push the rail into the rack until the quick release bracket snaps into place, securing the rail to the rack. Keep the rail horizontal.

The chassis package includes a rail set includes the outer rail pieces that attach to the rack Assembling the Outer Rails Each outer rail comes in two sections that must be assembled before mounting onto the rack. 2. Adjust the rail to reach just past the full depth of your rack. Assembling the Outer Rails 3. Align the square pegs on the rear end of the rail to the holes on the rack (D) and push the rail into the rack until the quick release bracket snaps into place, securing the rail to the rack. 1. Identify the left and right outer rails by examining the ends, which bend outward. Match the left front outer rail with the left rear outer rail and the same for the right rails. 2.

Align the round post in the rear rail (B) with the round hole at the end of the slot in the front rail (A), and slide the front section into the rear section. 4. Repeat the procedure for the other outer rail assembly. D Secure to the Rear of the Rack Slide Outer Rails Together Round Hole Secure to the Front of the Rack B A Assembling the Sections of the Outer Rail C Outer Rail Assembled Bracket with Square Pegs Figure 2-1. Assembling the Outer Rails Slide rail mounted equipment is not to be used as a shelf or a work space. Note: The figure above is for illustrative purposes only. Always install servers at the bottom of the rack first. Figure 2-2. Installing the Outer Rails to the Rack 21 20