4-2 Function Mode 4 Functions 4-102 Register No. Function name Parameter No. R/W Function Monitor or data range Resolution 1103h Multi-function input 1 selection C001 R/W 00: FW/01: RV/02: CF1/03: CF2/04: CF3/05: CF4/06: JG/07: DB/08: SET/09: 2CH/11: FRS/12: EXT/13: USP/15: SFT/ 16: AT/18: RS/19: PTC terminal 5 only/ 20: STA/21: STP/22: F/R/23: PID/24: PIDC/27: UP/28: DWN/29: UDC/31: OPE/50: ADD/51: F-TM/52: RDY/53: SP-SET/64: EMR(automatically allocated to terminal 3 if enabled)/255:
NO ⎯ 1532h 2nd multi-function input 1 selection C201 R/W 1104h Multi-function input 2 selection C002 R/W 1533h 2nd multi-function input 2 selection C202 R/W 1105h Multi-function input 3 selection C003 R/W 1534h 2nd multi-function input 3 selection C203 R/W 1106h Multi-function input 4 selection C004 R/W 1535h 2nd multi-function input 4 selection C204 R/W 1107h Multi-function input 5 selection C005 R/W 1536h 2nd multi-function input 5 selection C205 R/W 110Bh Multi-function input 1 operation selection C011 R/W 00: NO 01:
NC ⎯ 110Ch Multi-function input 2 operation selection C012 R/W 110Dh Multi-function input 3 operation selection C013 R/W 110Eh Multi-function input 4 operation selection C014 R/W 110Fh Multi-function input 5 operation selection C015 R/W 1114h Multi-function output terminal P1 selection C021 R/W 00: RUN/01: FA1/02: FA2/03: OL/04: OD/05: AL/06: Dc/07: FBV/08: NDc/09: LOG/10: ODc(Do not use.)/43: LOC ⎯ 1119h Relay output (MA, MB) function selection C026 R/W 111Bh AM selection C028 R/W 00: F (Output frequency) 01: A (Output current) ⎯ 111Dh Multi-function output terminal P1 contact selection C031 R/W 00: NO 01: NC ⎯ 1122h Relay output (MA, MB) contact selection C036 R/W 00: NO 01:
NC ⎯ 1178h Light load signal output mode C038 R/W 00: Enabled during acceleration/ deceleration/constant speed 01: Enabled only during constant speed ⎯ 1179h Light load detection level C039 R/W 0 to 20000 Set to10000 at rated current 0.01 [%]