4-2 Function Mode 4 Functions 4-103 Register No. Function name Parameter No. R/W Function Monitor or data range Resolution 1124h Overload warning level C041 R/W 0 to 20000 Set to10000 at rated current 0.01 [%] 153Ah 2nd overload warning level C241 R/W 1126h Arrival frequency during acceleration C042 R/W 0 to 4000 0.1 [Hz] 1128h Arrival frequency during deceleration C043 R/W 0 to 4000 0.1 [Hz] 1129h PID deviation excessive level C044 R/W 0 to 1000 0.1 [%] 112Eh PID FB upper limit C052 R/W 0 to 1000 0.1 [%] 112Fh PID FB lower limit C053 R/W 0 to 1000 0.1 [%] 1137h Operator/ModBus selection C070 ⎯ Do not change through ModBus communication. For setting, refer to "ModBus Setting" (4-78).
⎯ 1138h Communication speed selection (Baud rate selection) C071 ⎯ 1139h Communication station No. selection C072 ⎯ 113Bh Communication parity selection C074 ⎯ 113Ch Communication stop bit selection C075 ⎯ 113Dh Communication error selection C076 ⎯ 113Eh Communication error timeout C077 ⎯ 113Fh Communication wait time C078 ⎯ 1141h FV adjustment C081 R/W 0 to 2000 0.1 [%] 1142h FI adjustment C082 R/W 0 to 2000 0.1 [%] 1145h AM offset adjustment C086 R/W 0 to 100 0.1 [V] ⎯ Not used C091 ⎯ Do not change. ⎯ 1149h UP/DWN selection C101 R/W 00: OFF/01: ON ⎯ 114Ah Reset selection C102 R/W 00: Trip reset at power-on 01: Trip reset when the power is OFF 02:
Enabled only during trip (Reset when the power is ON.) ⎯ 1150h Logic operation function A input C141 R/W 00: RUN/01: FA1/02: FA2/03: OL/04: OD/05: AL/06: Dc/07: FBV/08: NDc/10: ODc(Do not use.)/43: LOC ⎯ 1151h Logic operation function B input C142 R/W 1152h Logic operator selection C143 R/W 00: AND/01: OR/02: XOR ⎯