Appendix-1 Parameter List Appendix * 2nd control is displayed when SET (08) is allocated to one of from C001 to C005. App-9 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value Restart during momentary power interruption b001 Retry selection 00: Alarm 01: 0 Hz start 02: Frequency matching start 03: Trip after frequency matching deceleration stop 00 No ⎯ b002 Allowable momentary power interruption time 0.3 to 25.0 1.0 No s b003 Retry wait time 0.3 to 100.0 1.0 No s b004 Momentary power interruption/ undervoltage trip during stop selection 00: Disabled 01:
Enabled 00 No ⎯ b005 Momentary power interruption retry time selection 00: 16 times 01: No limit 00 No ⎯ b011 Starting frequency at frequency pull- in restart 00: Frequency at interruption 01: Max. frequency 02: Set frequency 00 No ⎯ Electronic thermal b012 Electronic thermal level 0.2 × Rated current to 1.0 × Rated current Rated current No A b212 *2nd electronic thermal level Rated current b013 Electronic thermal characteristics selection 00: Reduced torque characteristics 1 01: Constant torque characteristics 02: Reduced torque characteristics 2 00 No ⎯ b213 *2nd electronic thermal characteristics selection 00