omron — Extended function mode

Appendix-1 Parameter List Appendix * 2nd control is displayed when SET (08) is allocated to one of from C001 to C005. App-10 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value Overload limit b021 Overload limit selection 00: Disabled 01: Enabled in acceleration/constant speed operation 02:

Enabled in constant speed operation 01 No ⎯ b221 *2nd overload limit selection 01 b022 Overload limit level 0..1 × Rated current to 1.5 × Rated current 1.5 × Rated current No A b222 *2nd overload limit level 1.5 × Rated current b023 Overload limit parameter 0.1 to 3000.0 1.0 No s b223 *2nd overload limit parameter 1.0 b028 Overload limit source selection 00: b022, b222 set values 01: Input terminal FV 00 No ⎯ b228 *2nd overload limit source selection 00 Frequency pull-in b029 Deceleration rate constant at frequency pull-in restart 0.1 to 3000.0 0.5 No s b030 Frequency pull-in restart level 0.2 × Rated current to 2.0 × Rated current Rated current No A Lock b031 Soft lock selection 00:

Data other than b031 cannot be changed when terminal SFT is ON. 01: Data other than b031 and the specified frequency parameter cannot be changed when terminal SFT is ON. 02: Data other than b031 cannot be changed. 03: Data other than b031 and the specified frequency parameter cannot be changed. 10: Data other than parameters changeable during operation cannot be changed. 01 No ⎯