Overview 2 Overview TwinCAT components TwinCAT embraces many system components which, together, constitute a complete solution for automation tasks: TwinCAT real time system: Real time expansion for Windows NT System Concept 8 Version: 1.0 Icon Description The TwinCAT software system is a complete automation system for PC-compatible computers, which is referred to as "The Windows Control and Automation Technology": TwinCAT transforms every compatible PC into a real time control with multi-PLC, NC axis control, a programming environment, and a control station. TwinCAT substitutes PLC and NC controllers as well as control stations with:
• open, compatible PC hardware, • programmed in accordance with the manufacturer-independent IEC61131-3 standard, • linking to all common field buses and PC interfaces for I/O signals, • embedding of PLC and NC systems in Windows NT, • data link to NT programs by means of open Microsoft standards (OLE, OCX, ActiveX, DCOM+, etc.). TwinCAT unites the real time control capability with the open and world-wide largest software platform of Microsoft's Windows operating systems.
Icon Description Programming of PLC programs for sequential logic in conformity with IEC61131-3, Programming of NC point-to-point (PTP) and interpolation (I) positioning in conformity with DIN66025, Real time system for the execution of PLC and NC programs in an exactly timed (deterministic) fashion, regardless of how the PC is used for further tasks, I/O linking for all widespread field buses and the PC interfaces and for third-party interface cards, Programming and data link with Windows applications ranging from visualisation to spreadsheet applications using OCX or DLL Icon Description TwinCAT features a real time expansion for Windows NT for the execution of automation programs in cycles as from 1 ms timed deterministically exact with a very small timing fluctuation (jitter) of only a few microseconds.
The TwinCAT real time expansion is a multitasking environment for the exactly timed control of "servers" that handle a very diverse range of tasks such as PLC, NC, PID and cam switching mechanisms etc. TwinCAT is integrated in Windows NT and, during the run time, it adds real time functions to it that are not intrinsically available in NT. The user does not modify NT for the operation of TwinCAT, i.e. it can be purchased, installed, used and maintained in the usual fashion. All properties of Windows NT are available without change during the operation of TwinCAT. The computing capacity that TwinCAT demands of the computer for real time tasks can be limited.
This setting remains fixed under all circumstances. A load display facilitates adjustment for the user.