Siemens — 14.1 SIRIUS 3RA6 compact starter

Technical data 14 14.1 SIRIUS 3RA6 compact starter General technical data Order number 3RA61 3RA62 Device standard IEC / EN 60947-6-2 Number of poles 3 Permissible ambient temperature Storage According to IEC / EN 60721-3-1 °C -55 to +80 Shipping Operation According to IEC / EN 60721-3-2 According to IEC / EN 60721-3-3 °C °C -55 to +80 -20 to +60 1) Permissible rated current of compact starter if - Several compact starters are installed side by side on a vertical DIN rail - Several compact starters are installed side by side on a SIRIUS 3RA6 infeed system Internal control cabinet temperature: + 40 °C Internal control cabinet temperature: + 60 °C % % 100 80 Max.

installation altitude m 2000 m above sea level without any restrictions Relative atmospheric humidity % 10 to 90 Max. rated current I r max (= max. rated operating current I e ) for the relevant setting range 0.1 ... 0.4 A 0.32 ... 1.25 A 1 ... 4 A 3 ... 12 A 8 ...

32 A A A A A A 0.4 1.25 4 12 32 Rated frequency Rated insulation voltage U i Hz V 50/60 690 Rated impulse voltage U imp kV 6 Trip class (CLASS) (the trip class corresponds to tolerance band E) According to IEC / EN 60947-6-2 10/20 1) At over 40 °C compact starter current reduction if - Several compact starters are installed side by side on a vertical DIN rail - Several compact starters are installed side by side on a SIRIUS 3RA6 infeed system SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 145