Technical data 14.1 SIRIUS 3RA6 compact starter Order number 3RA61 3RA62 Power loss P v max of all main current paths in accordance with rated current I r (top setting range) 0.1 ... 0.4 A 0.32 ... 1.25 A 1 ... 4 A 3 ... 12 A 8 ...
32 A mW mW W W W 2 19.1 0.2 0.7 2.3 Operating mechanism losses 24 V - Up to 12 A - 8 to 32 A Active power Active power W W 2.7 2.95 42 to 70 V - Up to 12 A - 8 to 32 A Active power Active power W W 2.5 3.0 110 to 240 V Active power Active power W W 3.4 3.8 - Up to 12 A - 8 to 32 A Overload function Ratio of lower to upper current mark 1:4 Degree of protection According to IEC / EN 60947-1 IP20 (connection compartment IP 00) Touch protection According to DIN EN 50274 Finger-safe Vibratory load f = 1 to 6 Hz; d = 15 mm 10 cycles f = 150 Hz; a = 2g Shock a = 60 m/sІ (6g) with 10 ms every 3 All axes subjected to shock Cooling None Conducted interference EMC interference immunity According to IEC / EN 60947-1 BURST according to IEC / EN 61000-4-4 kV Corresponds to degree of severity 3 4 Conducted interference SURGE according to IEC / EN 61000-4-5 - Conductor-ground - Conductor-conductor kV kV 4 1 Electrostatic discharge, According to IEC / EN 61000-4-2 kV 8 ESD Field-based interference suppression According to IEC / EN 61000-4-3 V/m 10 kV 6 Integrated auxiliary and signaling switches - Direct starter - Reversing starter Auxiliary switch Overload signaling switch Short circuit signaling switch 1 NO contact, 1 NC contact 1 CO contact 1 NO contact Auxiliary switch Overload signaling switch Short circuit signaling switch 2 NO contacts 1 CO contact 1 NO contact Extendable auxiliary switch block Direct starter:
1 x auxiliary switch block Reversing starter: 1 x auxiliary switch block per direction of rotation 2 NO contacts, 2 NC contacts, 1 NO contact, and 1 NC contact SIRIUS 3RA6 Compact Starter 146 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02