Technical data 14.1 SIRIUS 3RA6 compact starter Order number 3RA61 3RA62 Surge suppressor Varistor (ready-integrated) Degree of pollution 3 Safe isolation According to IEC / EN 60947-1 Control circuit to internal auxiliary circuit V 250 Internal auxiliary/control circuit to internal auxiliary/control circuit V 250 Internal auxiliary/control circuit to external auxiliary circuit V 400 Main circuit to internal auxiliary circuit Main circuit to external auxiliary circuit V V 400 400 Max. dimensions of direct starter Screw-type connection technology Spring-loaded connection technology W x H x D W x H x D mm mm 45 x 170 x 165 45 x 191 x 165 Max.
dimensions of reversing starter Screw-type connection technology Spring-loaded connection technology W x H x D W x H x D mm mm 90 x 170 x 165 90 x 191 x 165 Depth starting from DIN rail mm 160 Electromagnetic operating mechanism Order number 3RA61 3RA62 Frequency range Control voltage ranges V V V DC and 50/60 Hz (+/- 5%) 24 (AC/DC) 42 to 70 (AC/DC) 110 to 240 (AC/DC) Working range No-load operating frequency Where U S = control voltage 1/hour 3600 0.7 to 1.25 x U s OFF-delay time ms Max. 70 ON-delay time Max. breakaway starting current at 24 VDC ms Max.
120 - Up to 12 A - 8 to 32 A mA mA 250 350 Holding current and holding power valid for working range 24 V 24 V, AC operation - Up to 12 A Holding current Active power Apparent power cos φ mA W VA 132 2.7 3.15 0.86 - 8 to 32 A Holding current Active power Apparent power cos φ mA W VA 144 3.0 3.45 0.86 SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 147