Configuration 4.2 Supply possibilities in main circuit 4.2 Supply possibilities in main circuit The following supply options are available for the compact starter's main circuit: ● Infeed via parallel wiring of individual compact starters ● Infeed via SIRIUS infeed system for 3RA6 ● Infeed via 3-phase bus bars ● Infeed via 8US busbar adapter If the creepages and clearances specified by UL 508 also need to be observed, then special infeed terminals are available for the relevant infeed systems. According to UL 508, these infeed terminals are not required for MSP (Manual Starter Protector).
4.2.1 SIRIUS infeed system for 3RA6 Maximum rated current The following maximum rated currents apply to the components of the SIRIUS infeed system for 3RA6: Table 4-2 Maximum rated current (infeed system for 3RA6) SIRIUS 3RA6 Compact Starter 28 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 Components Order number Max rated current Ir max Left infeed, 50/70 mm² screw terminal with three slots, outgoing terminals with screw-type connection technology, incl. PE bar 3RA6813-8AB 100 A Left infeed, 50/70 mm² screw terminal with three slots, outgoing terminals with spring- loaded connection technology, incl.
PE bar 3RA6813-8AC 100 A Left infeed, 25/35 mm² screw terminal with three slots, outgoing terminals with screw-type connection technology, incl. PE bar 3RA6812-8AB 63 A Left infeed, 25/35 mm² screw terminal with three slots, outgoing terminals with spring- loaded connection technology, incl. PE bar 3RA6812-8AC 63 A Left or right infeed, 25/35 mm², with spring- loaded connection technology 3RA6830-5AC 63 A Extension connector 3RA6890-1AB 63 A