Configuration 4.2 Supply possibilities in main circuit WARNING Danger, high voltage! The maximum rated current for the extension connector is 63 A, regardless of the infeed block. If the rated current is exceeded, the extension connector will be damaged beyond repair. Make sure that the extension connector is never subjected to more than 63 A. Operating temperature The infeed system for 3RA6 has been designed for use with ambient temperatures ranging from - 20 °C to + 60 °C. Use with higher ambient temperatures The infeed system can be operated within the temperature range - 20 °C to + 40 °C without derating.
Within the temperature range + 40 °C to + 60 °C, derating of the compact starter's permissible rated current is necessary. SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 29 Internal control cabinet temperatures Permissible rated current Ir max of the compact starter + 40 °C 100% of Ir max + 60 °C 80% of Ir max