Configuration 4.2 Supply possibilities in main circuit Distance from neighboring components When installing the infeed system, the following distances from grounded or live parts and from neighboring components must be observed. ● Lateral distance from grounded parts: 10 mm ● Arcing space, top and bottom: 30 mm Figure 4-3 Distance of infeed system for 3RA6 from neighboring components (dimensions in mm) The installation guidelines for compact starters and circuit breakers/fuseless load feeders must also be observed along with the associated clearances.
Short-circuit protection The short-circuit protection device that is installed upstream of the infeed system must be designed in accordance with the table below.
Table 4-3 Short-circuit protection for SIRIUS infeed system for 3RA6 SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 31 ! ! ! ! Conductor cross-sections Id,max Recommendation regarding upstream short-circuit protection device (53 kA/400 VAC) Short-circuit protection for left or right infeed, 25/35 mm², with spring-loaded connection technology (3RA6830-5AC) 4 mm2 Id,max 5 kA, I2t = 85 kA2s 3RV1021-4DA10 6 mm2 Id,max .5 kA, I2t = 140 kA2s 3RV1031-4EA10 10 mm2 Id,max kA, I2t = 180 kA2s 3RV1031-4HA10 16 mm2/25 mm2 Id,max kA, I2t = 440 kA2s 3RV1041-4JA10