Configuration 4.2 Supply possibilities in main circuit Table 4-4 Short-circuit protection for terminal block (3RV1917-5D) On the 45 mm adapter for the infeed system for 3RA6 only S0 circuit breakers with a rated ultimate short-circuit breaking capacity I CU max = 12.5 A) may be mounted. If the short-circuit current at the installation point exceeds the circuit breaker's specified rated ultimate short-circuit breaking capacity, then you will need to use a backup fuse. WARNING Short-circuit hazard! Unless the cables running from the terminal block to the downstream short-circuit protection device are laid in a short-circuit proof manner, there is a risk of damage to the system.
Make sure that the cables running from the terminal block to the downstream short-circuit protection device are laid in a short-circuit proof manner (IEC / EN 60439-1 Section 7.5.5.1). SIRIUS 3RA6 Compact Starter 32 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 Conductor cross-sections Id,max Recommendation regarding upstream short-circuit protection device (53 kA/400 VAC) Short-circuit protection for - Left infeed, 25/35 mm² screw terminal with three slots, outgoing terminals with screw-type connection technology, incl. PE bar (3RA6812-8AB) - Left infeed, 50/70 mm² screw terminal with three slots, outgoing terminals with screw-type connection technology, incl.
PE bar (3RA6813-8AB) - Left infeed, 25/35 mm² screw terminal with three slots, outgoing terminals with spring-loaded connection technology, incl. PE bar (3RA6812-8AC) - Left infeed, 50/70 mm² screw terminal with three slots, outgoing terminals with spring-loaded connection technology, incl. PE bar (3RA6813-8AC) - - 3RV1041-4MA10 NH gL/gG 3NA3; 315 A Conductor cross-sections Id,max for downstream short-circuit protection device Short-circuit protection for terminal block (3RV1917-5D) 1.5 mm2 Id,max 2.5 mm2 Id,max 4 mm2 Id,max 6 mm2 Id,max