Functions 7 7.1 Normal switching duty Compact starters are mainly used for switching and protecting motors and also as main switches and disconnectors. The actuator can be used to switch the compact starter manually; together with the "ON I" LED it indicates the compact starter's current status. The actuator has three positions: ● READY: Compact starter is ready ● OFF: Compact starter is out of service ● TRIPPED: Malfunction or short circuit trip Actuator OFF When the actuator is in the OFF position, the main contacts are open and the active areas of the control electronics are disconnected. Only the thermal motor model and display elements remain in operation.
When the actuator is in the OFF position, the 3RA61 compact starter direct starter can adopt the following statuses: Table 7-1 Actuator display elements OFF (direct starter) SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 49 Actuator LEDs Compact starter status ON I A1/A2 OFF OFF OFF Compact starter is off: - The circuit breaker mechanism is off. - The main contacts are open. - The control voltage is not present. OFF OFF GREEN Compact starter is off: - The circuit breaker mechanism is off. - The main contacts are open. - The control voltage is present.