Functions 7.1 Normal switching duty When the actuator is in the OFF position, the 3RA62 compact starter reversing starter can adopt the following statuses: Table 7-2 Actuator display elements OFF (reversing starter) Actuator READY The circuit breaker mechanism (breaker latching mechanism) in the compact starter is switched on and the compact starter is ready. DANGER Machine start-up! Switch the actuator on the compact starter to READY with the "A1/A2" LED illuminated. The compact starter will switch on immediately and the machine will start up. Make sure that no-one is in the machine danger zone, when you move the actuator to the READY position.
When the actuator is in the READY position, the 3RA61 compact starter direct starter can adopt the following statuses: Table 7-3 Actuator display elements READY (direct starter) SIRIUS 3RA6 Compact Starter 50 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 Actuator LEDs Compact starter status ON I 1 ON I 2 A1/A2 B1/B2 OFF OFF OFF OFF Compact starter is off: - The circuit breaker mechanism is off. - The main contacts are open. - The control voltage is not present. OFF OFF OFF GREEN Compact starter is off: - The circuit breaker mechanism is off. - The main contacts are open. - The control voltage is present.
Actuator LEDs Compact starter status ON I A1/A2 READY OFF OFF Compact starter is ready: - The circuit breaker mechanism is on. - The main contacts are open. - The control voltage is not present. READY GREEN GREEN Compact starter is on: - The circuit breaker mechanism is on. - The main contacts are closed. - The control voltage is present. READY OFF GREEN Overload tripped