Siemens — 7.2 Overload protection function

Functions 7.2 Overload protection function 7.2 Overload protection function Function The compact starter protects three-phase motors against overload. Consequently, the compact starter can shut down without the breaker latching mechanism having to open. The compact starter is also equipped with phase failure protection in order to minimize heating of the load in the event of a phase failure during single-phase operation. For the purpose of the overload protection function, the rated current of the load is set using the "current setting I e " setting wheel. The overload trip class can be set to CLASS 10 or CLASS 20 directly on the device.

The "RESET M/A" (manual/automatic) selector switch allows you to select manual or auto reset following an overload: ● Manual reset: Following an overload, the compact starter is reset manually using the blue reset button. ● Auto reset: Following an overload, the compact starter is reset automatically after 3 minutes. However, a manual reset can still be performed if you have selected this setting. Display concept The "Overload tripped" status is indicated by the following elements: Table 7-6 Overload trip display elements (direct starter/reversing starter) Function test Use the "TEST " button to test the overload protection function ("overload protection function" test button).

The thermal motor model/overload protection function will not be affected by this function test. Use the "Test " button to switch the compact starter back on following a shutdown. Motor model The electronics calculate the motor temperature continuously in accordance with the operating time and current load and store this information in a thermal motor model. SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 53 Actuator Mech. display Compact starter status TRIP READY White display Overload tripped