Functions 7.2 Overload protection function Manual/auto reset +HDW QJWKHUPD PHPRU\ Figure 7-1 Manual/auto reset following an overload trip (t 1 ) Overload trip (t 2 ) Auto reset (t 3 ) Manual reset (t (t 4 ) Manual reset (t (t 5 ) Overload trip (t 6 ) Manual reset (t > 3 minutes following overload trip) If the "Manual/auto reset" selector switch is set to auto reset, any overload trip that occurs will be reset automatically after 3 minutes and the compact starter will be switched to READY. If the control voltage is present, the compact starter will switch on and the electronics will calculate the temperature increase of the motor model in accordance with the current flow (curve (2)).
DANGER Automatic machine restart! If the compact starter is set to auto reset, it will be reset automatically following an overload trip. Assuming that the control voltage is present at this moment, the compact starter will switch on automatically and the machine will start up. Make sure that the machine danger zone is kept clear of people at all times. A manual reset can always be performed regardless of the "Manual/auto reset" selector switch position. However, if the "Manual/auto reset" selector switch is set to manual reset, the compact starter can only be reset manually. The compact starter is set to READY again by pressing the "Reset overload trip" button.
If the control voltage is present at this moment, the compact starter will switch on and the electronics will calculate the temperature increase of the motor model in accordance with the current flow (curves (3) and (6)). SIRIUS 3RA6 Compact Starter 54 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 W W W W W W 7LPH >W@ W