Siemens — 7.2 Overload protection function

Functions 7.2 Overload protection function NOTICE If a manual reset is performed within 3 minutes of the overload trip and the compact starter switches on, there is a risk of a new overload trip occurring immediately due to the fact that the motor/motor model may not yet have had a chance to cool down sufficiently (curve (4)). Risk of a new overload trip! Make sure that the motor has cooled down sufficiently before resetting the compact starter. If there is no control voltage present following a manual or automatic reset, the motor model will continue to cool down as per the motor (curve (1)). SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 55