Functions 7.3 Short-circuit protection function 7.3 Short-circuit protection function Function The SIRIUS 3RA6 compact starter's short-circuit releases are designed to isolate the faulty load feeder from the supply system in the event of a short circuit in order to prevent any further damage. The short-circuit release is factory set to 14 times the maximum rated current I n of the compact starter. The compact starter has a short-circuit switching capacity of 53 kA at a voltage of 400 VAC. Overload trips and short-circuit trips are signaled via two separate signaling switches so that both signals can be evaluated in their own right.
For additional information on terminal assignment, please refer to "Connecting the compact starter without optional AS-i mounting module (Page 75)". Display concept The "Short circuit tripped" status is indicated by the following elements: Table 7-7 Short circuit trip display elements (direct starter/reversing starter) Resetting the short circuit trip WARNING Short-circuit hazard! If the short circuit trip is reset on the compact starter before the cause of the short circuit has been eliminated, a new short circuit will occur when the compact starter commences operation.
Eliminate the cause of the short circuit before resetting the short circuit trip on the compact starter and putting the compact starter back into operation. To reset a short circuit trip, turn the actuator to the OFF position. Function test To test the short-circuit protection function, press the "TEST I>>" button ("Short-circuit protection" test button). SIRIUS 3RA6 Compact Starter 56 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 Actuator Mech. display RLT 0% Compact starter status TRIPPED No display Short circuit tripped