Functions 7.4 Shutdown on malfunction 7.4 Shutdown on malfunction Type of malfunction There is a patented mechanism for detecting malfunctions, which opens the main contacts. The following malfunctions can be detected: ● End of service life – Worn switching contacts. (For additional information on electrical endurance, please refer to "Technical data (Page 145)".) – Worn switching mechanism. (For additional information on mechanical service life, please refer to "Technical data (Page 145)".) ● Faults in the control electronics Display concept The "Malfunction" status is indicated by the following elements:
Table 7-8 Malfunction display elements (direct starter/reversing starter) Eliminating malfunctions CAUTION There is a malfunction on the compact starter. A compact starter malfunction will cause the compact starter to shut down. Continuing to operate the compact starter is extremely risky, as it can no longer be considered reliable. Following a shutdown caused by a malfunction, you will need to replace the compact starter. In order to achieve a safe system status, you can continue operating the compact starter for a short time. For this purpose, you will have to set the compact starter to "ready" again by turning the actuator to the OFF position and then to the READY position.
Note Once the malfunction has been reset, the white field will continue to be displayed in the "RLT 0%" display window. The compact starter must be replaced. SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 57 Actuator Mech. display RLT 0% Compact starter status TRIPPED White display Malfunction (e.g. end of service life reached)