Siemens — 10.1 Settings on the compact starter

Commissioning 10 10.1 Settings on the compact starter All settings are made on the device itself. CLASS 10/20 The CLASS (overload trip class) indicates the tripping time t A of the compact starter (from cold) at 7.2 times the current setting I e . As the compact starter features a solid-state overload relay, the trip class corresponds to the narrow tolerance band E (IEC / EN 60947-6-2): ● CLASS 10: 5 s A ● CLASS 20: 10 s A The trip class can be set to CLASS 10 or CLASS 20 using a slide switch. Current setting I e The rated operating current of the motor requiring protection is set on the setting scale.

RESET M/A The "RESET M/A" (manual/automatic) selector switch allows you to select manual or auto reset following an overload trip: ● Manual reset: Following an overload trip, the compact starter is reset manually using the blue reset button. ● Auto reset: Following an overload trip, the compact starter is reset automatically after 3 minutes. However, a manual reset can still be performed if you have selected this setting. For additional information on the manual and auto reset functions, please refer to "Overload protection function (Page 53)". SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 81