Siemens — 10.2.1 Addressing via AS-Interface

Commissioning 10.2 AS-Interface 10.2 AS-Interface 10.2.1 Addressing via AS-Interface Before it can participate in data exchange with the master, each module must be assigned an individual address on the AS-Interface. Each address can only be used once on each AS-i network. On the AS-i mounting module, an extended master can be used to access the extended address mode (A/B technology). The 31 addresses that are supported by an AS-Interface network can be split into two completely separate sub-addresses, e.g. 1A and 1B. If you do decide to use this facility for all 31 slaves, there will be a maximum of 62 nodes on one AS-Interface network.

AS-i profile Table 10-1 AS-i profile (AS-i mounting module) *) User-adjustable Requirements Danger, high voltage! WARNING Electrical voltage can result in electric shocks or burns. Disconnect the AS-i voltage before you start the addressing process. To carry out the AS-i mounting module addressing, you will need the following: ● An AS-i addressing unit (3RK1904-2AB01) or programming and service unit plus connected AS-i power supply or GOSSEN GMC Metratest 36 AS-i ● A connecting cable for connecting the AS-Interface addressing unit to the AS-i mounting module.

SIRIUS 3RA6 Compact Starter 82 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 I/O configuration (Hex) ID code (Hex) ID1 code (Hex) ID2 code (Hex) 7 A 1 ... 7 *) Factory setting: 7 E