Configuration | ADS 4.3.2.2 Blacklisting and whitelisting | Blacklisting and whitelisting With version 1.12, it is possible to use black or whitelisting for PLC symbols. With black or whitelisting, PLC symbols can be explicitly hidden or shown for use in the HMI. For this, you can tag the corresponding variables in the PLC with an attribute pragma . In the default case, blacklisting is active, which means that you have access to all variables of the PLC that are not explicitly hidden for the HMI. On the configuration page of the ADS extension, you can switch between black and whitelisting ( Use whitelisting ).
The following attribute pragmas are available for black or whitelisting in the TwinCAT HMI: { attribute 'TcHmiSymbol.Show' } { attribute 'TcHmiSymbol.ShowRecursively' } { attribute 'TcHmiSymbol.Hide' } { attribute 'TcHmiSymbol.ReadOnly' } { attribute 'TcHmiSymbol.BLOB' } Use : TcHmiSymbol.Show: If a variable has this attribute, it will be displayed in the HMI in case of whitelisting. With this attribute only the first level is displayed (example: only the struct, but not the sub- elements). The attribute has no effect on blacklisting. TF2000 39 Version: 1.8.0