PLC API stParams consists of the following elements: TYPE ST_CTRL_PT2_PARAMS : STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; fKp : FLOAT := 0; tT1 : TIME := T#0ms; tT2 : TIME := T#0ms; END_STRUCT END_TYPE 4.2.1.4.11 FB_CTRL_PT2oscillation The function block provides an oscillating PT2 transfer element in the functional diagram. Transfer function 1 ( ) 1 2 p G s K T s T s J = + + 2 2 0 0 TF4100 104 Version: 2.2.4 Name Type Description stParams ST CTRL PT2 _ _ _ PARAMS Parameter structure of the PT2 element Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime.
The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. fKp FLOAT Controller amplification / transfer coefficient tT1 TIME Time constant T1 tT2 TIME Time constant T2