PLC API Inputs/ outputs VAR_IN_OUT stParams : ST_CTRL_SPLITRANGE_PARAMS; END_VAR stParams consists of the following elements: TYPE ST_CTRL_SPLITRANGE_PARAMS: STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; bInvertNegOutput : BOOL; bDisablePosOut : BOOL; bDisableNegOut : BOOL; END_STRUCT END_TYPE 4.2.1.7.9 FB_CTRL_STEPPING_MOTOR_OUT This function block generates a control value for a stepper motor. TF4100 150 Version:
2.2.4 Name Type Description fOutPos FLOAT Positive part of fIn fOutNeg FLOAT Negative part of fIn bOutPosIsActive BOOL TRUE indicates "fIn > 0.0" bOutNegIsActive BOOL TRUE indicates "fIn eErrorId E CTRL ERROR _ _ CODES Supplies the error number [} 173] when the output bError is set. bError BOOL Becomes TRUE, as soon as an error occurs. Name Type Description stParams ST CTRL SPLIT _ _ RANGE _ PARAMS Parameter structure of the function block Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime.
The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. bInvertNegOutpu t BOOL fOutNeg is inverted when this parameter is TRUE. bDisablePosOut BOOL The output fOutPos is disabled and always "0.0“. bDisableNegOut BOOL The output fOutNeg is disabled and always "0.0“.