beckhoff TF4100 — 4.2.1.7.9 FB_CTRL_STEPPING_MOTOR_OUT

PLC API Behavior of the output Inputs VAR_INPUT fIn : FLOAT; bUpperLimitSwitch : BOOL; bLowerLimitSwitch : BOOL; fManSyncValue : FLOAT; bSync : BOOL; eMode : E_CTRL_MODE; END_VAR For synchronization with the current valve position, this function block has the mode eCTRL_MODE_SYNC_MOVEMENT . In this mode, pulses for closing the valve are output until the valve is safely closed. The function block is then synchronized with this valve position. Once the synchronization process is completed, eCTRL_STATE_ACTIVE mode is automatically activated. TF4100 151 Version:

2.2.4 Name Type Description fIn FLOAT Controller's control value (controller output) bUpperLimit Switch BOOL Limit switch, becomes TRUE when the upper stop is reached. bLowerLimit Switch BOOL Limit switch, becomes TRUE when the lower stop is reached. fManSyncValue FLOAT Input with which the internal state of the motor setting can be adjusted, or whose value is adopted in manual mode. bSync BOOL With a rising edge at this input the internal step counter is set to the step that corresponds to the value "fManSyncValue". eMode E CTRL MODE _ _ Input that specifies the operation mode [} 173] of the function block.