beckhoff TF4100 — 4.2.1.2.3 FB_CTRL_I

PLC API VAR_IN_OUT stParams :ST_CTRL_P_PARAMS; END_VAR Inputs/ outputs stParams consists of the following elements: TYPE ST_CTRL_P_PARAMS: STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; fKp : FLOAT := 0.0; END_STRUCT END_TYPE 4.2.1.2.3 FB_CTRL_I The function block provides an I-transfer element in the functional diagram. Transfer function I G s T s = 1 ( ) TF4100 29 Version: 2.2.4 Name Type Description fOut FLOAT Output of the P element eState E CTRL STATE _ _ State of the function block eErrorId E CTRL ERROR _ _ CODES Supplies the error number [} 173] when the output bError is set. bError BOOL Becomes TRUE, as soon as an error occurs.

Name Type Description stParams ST CTRL P _ _ _ PARAMS Parameter structure of the P element Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. fKp FLOAT Proportional gain of the P-element