beckhoff TF4100 — 4.2.1.2.3 FB_CTRL_I

PLC API Inputs VAR_INPUT fIn : FLOAT; fManSyncValue : FLOAT; bSync : BOOL; eMode : E_CTRL_MODE; bHold : BOOL; END_VAR VAR_OUTPUT fOut : FLOAT; bARWactive : BOOL; eState : E_CTRL_STATE; eErrorId : E_CTRL_ERRORCODES; bError : BOOL; END_VAR Outputs Inputs/ outputs VAR_IN_OUT stParams : ST_CTRL_I_PARAMS; END_VAR stParams consists of the following elements: TYPE ST_CTRL_I_PARAMS: STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; tTi : TIME := T#0ms; fOutMaxLimit : FLOAT := 1E38; fOutMinLimit : FLOAT := -1E38; END_STRUCT END_TYPE TF4100 30 Version:

2.2.4 Name Type Description fIn FLOAT Input of the I element fManSyncValue FLOAT Input to which the I-element can be synchronized, or whose value is the present at the output in Manual Mode. bSync BOOL A rising edge at this input sets the integrator to the value "fManSyncValue". eMode E CTRL MODE _ _ Input that specifies the operation mode of the function block. bHold BOOL A TRUE at this input holds the integrator fixed at the current value, independently of the input fIn. Name Type Description fOut FLOAT Output of the I element bARWactive BOOL A TRUE at this output indicates that the integrator is being restricted.

eState E CTRL STATE _ _ State of the function block eErrorId E CTRL ERROR _ _ CODES Supplies the error number when the output bError is set. bError BOOL Becomes TRUE, as soon as an error occurs. Name Type Description stParams ST CTRL I _ __ PARAMS Parameter structure of the I element