beckhoff TF4100 — 4.2.1.3.10 FB_CTRL_PID_EXT_SPLITRANGE

PLC API VAR_IN_OUT stParams : ST_CTRL_PID_EXT_SPLITRANGE_PARAMS; END_VAR Inputs/ outputs stParams consists of the following elements: TYPE ST_CTRL_PID_EXT_SPLITRANGE_PARAMS : STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; fKp_heating : FLOAT := 0; tTn_heating : TIME := T#0ms; tTv_heating : TIME := T#0ms; tTd_heating : TIME := T#0ms; fKp_cooling : FLOAT := 0; tTn_cooling : TIME := T#0ms; tTv_cooling : TIME := T#0ms; tTd_cooling : TIME := T#0ms; nParameterChangeCycleTicks : INT; fDeadBandInput : REAL := 0.0; fDeadBandOutput : REAL := 0.0; fInnerWindow : REAL := 0.0; fOuterWindow : REAL := 0.0; fOutMaxLimit : FLOAT := 1E38; fOutMinLimit :

FLOAT := -1E38; bPInTheFeedbackPath : BOOL; bDInTheFeedbackPath : BOOL; bARWOnIPartOnly : BOOL; END_STRUCT END_TYPE TF4100 70 Version: 2.2.4 Name Type Description fOutPos FLOAT Output of the PID-element when the control value is positive. A zero is output otherwise. fOutNeg FLOAT Output of the PID-element when the control value is negative. A zero is output otherwise. fOut FLOAT Output of the PID element bARWActive BOOL A TRUE at this output indicates that the PID-element is being restricted. bParameter ChangeActive BOOL A TRUE at this output indicates that the change from one parameter set to the other is in progress. bError BOOL Becomes TRUE, as soon as an error occurs.

eErrorId E CTRL ERROR _ _ CODES Supplies the error number [} 173] when the output bError is set. fCtrlDerivation A TRUE at this output indicates that the PID-element is being restricted. Name Type Description stParams ST CTRL _ _ PID EXT SPLIT _ _ RANGE PARAMS _ Parameter structure of the PID element