beckhoff TF4100 — 4.2.1.3.10 FB_CTRL_PID_EXT_SPLITRANGE

PLC API TF4100 71 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. Range eCTRL PARAMETER RECORD HEATING: _ _ _ fKp heating _ FLOAT Controller amplification / controller coefficient tTn heating _ TIME Integral action time:

The I-component is deactivated if this is parameterized as T#0s. tTv heating _ TIME Derivative action time: The D-component is deactivated if this is parameterized as T#0s. tTd heating _ TIME Damping time Range eCTRL PARAMETER RECORD COOLING: _ _ _ fKp cooling _ FLOAT Controller amplification / controller coefficient tTn cooling _ TIME Integral action time: The I-component is deactivated if this is parameterized as T#0s. tTv cooling _ TIME Derivative action time: The D-component is deactivated if this is parameterized as T#0s. tTd cooling _ TIME Damping time nParameter ChangeCycle Ticks INT The number of task cycles over which the change from one parameter set to the other takes place.

fDeadBandInput REAL See description above: Input dead band fDeadBandOutpu t REAL See description above: Output dead band fInnerWindow REAL See description above: Linear reduction of the I-component in the Inner Window fOuterWindow REAL See description above: Switching off the I-component in the Outer Window fOutMaxLimit FLOAT Upper limit at which integration is halted and to which the output is limited (ARW measure). Reaching this limit is indicated by a TRUE at the bARWActive output. fOutMinLimit FLOAT Lower limit at which integration is halted and to which the output is limited (ARW measure). Reaching this limit is indicated by a TRUE at the bARWActive output.

bPInTheFeed backPath BOOL Input value of the P-element can be selected with this input (see functional diagram). bDInTheFeed backPath BOOL Input value of the D-element can be selected with this input (see functional diagram). bARWOnIPart Only BOOL If this parameter is FALSE (the standard setting), the integration of the I-component is halted if the complete controller output reaches the upper or lower limit. If it is TRUE, the integration is halted if the I-component (the output of the integrator) reaches some limit. (Cf. functional diagram.)