beckhoff TS1110 — 4.1.1 Profiles supported by the TwinCAT Simulation Manager

Tutorials Table 3: Types of data mappings Original mode Figure 1 [ } 15] shows a TwinCAT system configuration in non-simulated (original) mode. The active mappings indicated with red and yellow run between the I/O devices and the original PLCs. The mappings indicated in grey to/from the simulation PLC are inactive. This means that the original PLCs communicate with the I/O devices, which must be present and active. The simulation PLC is inactive and does not participate in the communication (original mode) Fig. 2: Figure 1:

TwinCAT System in original mode The links / mappings from / to the Simulation PLC can represent local or remote connections, dependant of the location of the Simulation PLC. TS1110 15 Version: 1.0 Type of mapping Description A device input or output is observed. That is the device inputs or outputs are available at a simulation input and are available there for further processing. In original mode, the mapping to stimulation PLC does not exist. Simulating Simulation of an I/O, the mapping and the device are removed in simulation mode. The mapping between device input and the original PLC input (or device output and original PLC output) is separated and "simulated" by the simulation PLC.

This means that for inputs the simulation PLC delivers the values for the original PLCs or for outputs the original PLC values are fed into the simulation PLC. In original mode, this "diversion" is inactive. Original No change in simulation mode. Communication between original PLC and device remains active (if device is not "deactivated", see Deactivating device [} 16]