PLC API 6.4 FB_SimRamp Ramp block A signal that changes linearly over time can be simulated via the ramp block. The signal initialises with the value ' fStart ' and ends after a time ' tRampTime ' with the value ' fTarget '. VAR_INPUT VAR_INPUT bEnable : BOOL; (* Starts ramp with rising edge, Stops ramp with falling edge *) fStart : REAL; (* Start value *) fTarget : REAL; (* Target value *) tRampTime : TIME; (* Time needed from fStart to fTarget *) END_VAR bEnable : The ramp is started with a rising edge, and stopped with a falling one fStart : Start value fTarget : Target value tRampTime : Time duration from fStart to fTarget VAR_OUTPUT VAR_OUTPUT fOut :

REAL; (* Output value *) bValueReached : BOOL; (* Target value reached *) END_VAR fOut : Current value bValueReached : TRUE : Target value reached Requirements 6.5 FB_SimDerivative Derivative block TS1110 60 Version: 1.0 Development Environment Target System PLC Libraries to include TwinCAT v2.9.0 Build > 1020 PC (i386) TcSimManager.Lib (Standard.Lib; TcBase.Lib; TcSystem.Lib are included automatically)