FAQs (frequently asked questions) 8 FAQs (frequently asked questions) Error Message: "The system manager configuration file 'XXX.wsm' cannot be opened. The file is probably blocked by another system manager instance!" [ } 79] Error Message: "The PlcControl symbol file for the project 'XXX' has not been found. The system manager configuration must be corrected before it can be used!" [ } 80] The newly created simulation PLC project does not contain any inputs or outputs. [ } 80] The system reports "The system manager configuration file 'XXX.wsm' cannot be opened. The file is probably blocked by another system manager instance!" Problem:
The 'TwinCAT System Manager' is addressed by the 'TwinCAT Simulation Manager' as the 'Out-of-process' COM server. They run as two separate processes (EXE files) that communicate with each other. This fault message is displayed when a system manager process can no longer be addressed. The system is blocked as a second system manager instance cannot be started on the same configuration file. Solution: The blocked system manager process must be exited. To this end, please carry out the following operations: 1. Router cleanup (in some cases this step alone is enough) TS1110 79 Version: 1.0