beckhoff TS6120 — 6.1.2 Data Access

Configuration 6.1.2 Data Access An OPC server represents a standardised interface for the management of process data. The process data available in the TwinCAT system must therefore be known to the OPC server, or must be made known to it at the time of configuration. To represent this "hierarchical process space" clearly, the "Devices" are subdivided into subsidiary items. The OPC client can browse through this representation and use it for the server's actual configuration. The TwinCAT OPC server supports the optional browser OPC interface. This hierarchical display is not to be confused with the configuration of the OPC server that exists at run-time.

The run-time configuration of the OPC server, i.e. the creation of groups, specification of the refresh time, the insertion of tags etc. is performed dynamically by the OPC client. General The advantage of configuration via XML with links to the symbols of the ADS devices is that this configuration only must be carried out once. Even if, for instance, the PLC project changes (e.g. if variables are deleted, or if new variables are defined) it is not necessary to change the configuration in the OPC server: each time the OPC service starts, the namespace of the OPC server is correctly built up. Device Definition A device represents a TwinCAT ADS device (e.g.

a PLC run-time system) that is uniquely identified by the and the . Further information about the concept of devices in TwinCAT can be found in the general TwinCAT ADS documentation. TS6120 18 Version: 1.2.0 Type Req./Opt. Description ConversionID Req unique ID-number which identifies this conversion ConversionDesc Optional ConversionType Req 0 : NoConversion 1 : LinearConversion Clamping Optional 0 : No clamping 1 : Clamp on EU 2 : Clamp as specified If clamping is active, the data value will be limited to its High clamp/EU value, when it exceeds the upper limit, and similarly with Low clamp parameter.

HighClamp Optional, depends on / 1.0 (Default) LowClamp Optional, depends on / 0.0 (Default) HighEU Optional, depends on / engineering unit (client scale) 1.0 (Default) LowEU Optional, depends on / engineering unit (client scale) 0.0 (Default) HighIR Optional, depends on / instrument range (device scale) 10000 (Default) LowIR Optional, depends on / instrument range (device scale) 0 (Default)