TwinCAT library and programming str_Date : Returns the date of installation of the device in the format . bError : If an error should occur during the transmission of the command, this output is set after the bBusy output has been reset. iErrorID : Supplies an ADS error number when the output bError is set. Requirements 6.1.5 FB_PN_IM2_WRITE Using this function block the PROFINET controller writes all I&M 2 data (Identification & Maintenance) data to a device referenced via the Port input. The frame structure of the I&M2 function corresponds to the index 0xAFF2 [ } 67] according to PROFINET standard. VAR_INPUT VAR_INPUT bStart : BOOL; NETID :
T_AmsNetId;(* AMS Net ID from Controller *) PORT : T_AmsPort; (* Port used by Controller to communicate with Device *) str_Date : TIMESTRUCT;(*YYYY-MM-DD HH:MM*) END_VAR bStart : The block is activated by a rising edge on this input NETID : AMS Net ID of the controller PORT : Port via which the controller communicates with the device (port = Device ID + 1000hex) str_Date : Writes a date (e.g. date of installation of the device) to the device in the format HH:MM >. VAR_OUTPUT VAR_OUTPUT bBusy : BOOL; bError : BOOL; iErrorID : UDINT; END_VAR bBusy : When the function block is activated this output is set. It remains set until feedback is received.
While Busy = TRUE, no new command will be accepted at the inputs. bError : If an error should occur during the transmission of the command, this output is set after the bBusy output has been reset. iErrorID : Supplies an ADS error number when the output bError is set. TS6271 58 Version: 1.2 Development environment Target platform PLC libraries to be linked TwinCAT v2.11.0 R3 PC or CX (x86, ARM) TcProfinetDiag.Lib