TwinCAT library and programming Requirements 6.1.6 FB_PN_IM3_READ Using this function block the PROFINET controller reads all I&M3 data (Identification & Maintenance) from a device referenced via the Port input. The frame structure of the I&M3 function corresponds to the index 0xAFF3 [ } 67] according to PROFINET standard. VAR_INPUT VAR_INPUT bStart : BOOL; NETID : T_AmsNetId;(* AMS Net ID from Controller *) PORT : T_AmsPort; (* Port used by Controller to communicate with Device *) END_VAR bStart : The block is activated by a rising edge on this input NETID : AMS Net ID of the controller PORT :
Port via which the controller communicates with the device (port = Device ID + 1000hex) VAR_OUTPUT VAR_OUTPUT bBusy : BOOL; st_IM_Descriptor : STRING(54); bError : BOOL; iErrorID : UDINT; END_VAR bBusy : When the function block is activated this output is set. It remains set until a feedback is received. While Busy = TRUE, no new command will be accepted at the inputs. st_IM_Descriptor : Returns the manufacturer description stored for the device. bError : If an error should occur during the transmission of the command, this output is set after the bBusy output has been reset. iErrorID : Supplies an ADS error number when the output bError is set. Requirements TS6271 59 Version:
1.2 Development environment Target platform PLC libraries to be linked TwinCAT v2.11.0 R3 PC or CX (x86, ARM) TcProfinetDiag.Lib Development environment Target platform PLC libraries to be linked TwinCAT v2.11.0 R3 PC or CX (x86, ARM) TcProfinetDiag.Lib