PLC libraries sIPAddr : Is a string containing the IP address of the target device. nTCPPort : Port number of the target device. nUnitID : Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nQuantity : Number of digital inputs (data bits) to be read. The value of nQuantity must be > 0. nMBAddr: Start address of the digital inputs to be read (bit offset). cbLength : Contains the max. byte size of the destination buffer. The minimum buffer byte size must be: (nQuantity + 7) / 8 . pDestAddr : Contains the address of the destination buffer into which the data are to be read.
The buffer can be a single variable, an array or a structure, whose address can be found with the ADR operator. bExecute : The function block is activated by a rising edge at this input. tTimeout : States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBUSY : BOOL; bError : BOOL; nErrId : UDINT; cbRead : UDINT; END_VAR bBusy : When the function block is activated this output is set. It remains set until an acknowledgement is received. bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId : Supplies the ADS error number when the bError output is set.
cbRead: Contains the number of bytes currently read. Requirements TS6250 39 Version: 1.2 Function specific ADS error code Possible reason 0x8001 Modbus function not implemented 0x8002 Invalid address or length 0x8003 Invalid parameters: - wrong number of registers 0x8004 Modbus server error Development environment Target system type PLC libraries to be linked TwinCAT v2.8.0 PC (i386) TcModbusSrv.Lib