beckhoff TS6250 — 7.1.11.3 FB_MBUdpReadRegs (Modbus function 3)

PLC libraries 7.1.11.3 FB_MBUdpReadRegs (Modbus function 3) This function is used for reading 1 to 128 output registers (16 bit). The first byte contains the lower eight bits and the second byte the upper eight bits. VAR_INPUT VAR_INPUT sIPAddr : STRING(15); nTCPPort : UINT:= MODBUS_TCP_PORT; nUnitID : BYTE:=16#FF; nQuantity : WORD; nMBAddr : WORD; cbLength : UDINT; pDestAddr : UDINT; bExecute : BOOL; tTimeout : TIME; END_VAR sIPAddr : Is a string containing the IP address of the target device. nTCPPort : Port number of the target device. nUnitID : Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nQuantity :

Number of output registers (data words) to be read. The value of nQuantity must be > 0. nMBAddr: Start address of the output registers to be read (word offset). cbLength : Contains the max. byte size of the destination buffer. The minimum buffer byte size must be: nQuantity * 2 . pDestAddr : Contains the address of the destination buffer into which the data are to be read. The buffer can be a single variable, an array or a structure, whose address can be found with the ADR operator. bExecute : The function block is activated by a rising edge at this input. tTimeout : States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBUSY :

BOOL; bError : BOOL; nErrId : UDINT; cbRead : UDINT; END_VAR bBusy : When the function block is activated this output is set. It remains set until an acknowledgement is received. bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId : Supplies the ADS error number when the bError output is set. TS6250 40 Version: 1.2