beckhoff TS6250 — 7.1.11.4 FB_MBUdpReadInputRegs (Modbus function 4)

PLC libraries cbRead: Contains the number of bytes currently read. Requirements 7.1.11.4 FB_MBUdpReadInputRegs (Modbus function 4) This function is used for reading 1 to 128 input registers (16 bit). Endian VAR_INPUT VAR_INPUT sIPAddr : STRING(15); nTCPPort : UINT:= MODBUS_TCP_PORT; nUnitID : BYTE:=16#FF; nQuantity : WORD; nMBAddr : WORD; cbLength : UDINT; pDestAddr : UDINT; bExecute : BOOL; tTimeout : TIME; END_VAR sIPAddr : Is a string containing the IP address of the target device. nTCPPort : Port number of the target device. nUnitID : Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nQuantity :

Number of input registers (data words) to be read. The value of nQuantity must be > 0. nMBAddr: Start address of the input register to be read (word offset). cbLength : Contains the max. byte size of the destination buffer. The minimum buffer byte size must be: nQuantity * 2 . pDestAddr : Contains the address of the destination buffer into which the data are to be read. The buffer can be a single variable, an array or a structure, whose address can be found with the ADR operator. bExecute : The function block is activated by a rising edge at this input. TS6250 41 Version:

1.2 Function specific ADS error code Possible reason 0x8001 Modbus function not implemented 0x8002 Invalid address or length 0x8003 Invalid parameters: - wrong number of registers 0x8004 Modbus server error Development environment Target system type PLC libraries to be linked TwinCAT v2.8.0 PC (i386) TcModbusSrv.Lib