PLC libraries tTimeout : States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBUSY : BOOL; bError : BOOL; nErrId : UDINT; cbRead : UDINT; END_VAR bBusy : When the function block is activated this output is set. It remains set until an acknowledgement is received. bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId : Supplies the ADS error number when the bError output is set. cbRead: Contains the number of bytes currently read.
Requirements 7.1.11.5 FB_MBUdpWriteSingleCoil (Modbus function 5) This function is used for writing a single digital output (coil). Bit access is used. VAR_INPUT VAR_INPUT sIPAddr : STRING(15); nTCPPort : UINT:= MODBUS_TCP_PORT; nUnitID : BYTE:=16#FF; nMBAddr : WORD; nValue : WORD; bExecute : BOOL; tTimeout : TIME; END_VAR sIPAddr : Is a string containing the IP address of the target device. nTCPPort : Port number of the target device. TS6250 42 Version: 1.2 Function specific ADS error code Possible reason 0x8001 Modbus function not implemented 0x8002 Invalid address or length 0x8003 Invalid parameters:
- wrong number of registers 0x8004 Modbus server error Development environment Target system type PLC libraries to be linked TwinCAT v2.8.0 PC (i386) TcModbusSrv.Lib