beckhoff TS6250 — 7.1.11.6 FB_MBUdpWriteSingleReg (Modbus function 6)

PLC libraries nUnitID : Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nMBAddr: Address of the digital output (bit offset). nValue: Value to be written into the digital output. The value 16#FF00 switches the output on, 16#0000 switches it off. bExecute : The function block is activated by a rising edge at this input. tTimeout : States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBUSY : BOOL; bError : BOOL; nErrId : UDINT; END_VAR bBusy : When the function block is activated this output is set. It remains set until an acknowledgement is received.

bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId : Supplies the ADS error number when the bError output is set. Requirements 7.1.11.6 FB_MBUdpWriteSingleReg (Modbus function 6) This function is used for writing an individual output register. 16 bit access is used. VAR_INPUT VAR_INPUT sIPAddr : STRING(15); nTCPPort : UINT:= MODBUS_TCP_PORT; nUnitID : BYTE:=16#FF; nMBAddr : WORD; nValue : WORD; TS6250 43 Version: 1.2 Function specific ADS error code Possible reason 0x8001 Modbus function not implemented 0x8002 Invalid address or length 0x8003 Invalid parameters:

- wrong number of registers 0x8004 Modbus server error Development environment Target system type PLC libraries to be linked TwinCAT v2.8.0 PC (i386) TcModbusSrv.Lib