PLC libraries bExecute : BOOL; tTimeout : TIME; END_VAR sIPAddr : Is a string containing the IP address of the target device. nTCPPort : Port number of the target device. nUnitID : Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nMBAddr : Address of the output register (word offset). nValue : Value to be written into the register (word value). bExecute : The function block is activated by a rising edge at this input. tTimeout : States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBUSY : BOOL; bError : BOOL; nErrId : UDINT; END_VAR bBusy :
When the function block is activated this output is set. It remains set until an acknowledgement is received. bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId : Supplies the ADS error number when the bError output is set. Requirements 7.1.11.7 FB_MBUdpWriteCoils (Modbus function 15) TS6250 44 Version: 1.2 Function specific ADS error code Possible reason 0x8001 Modbus function not implemented 0x8002 Invalid address or length 0x8003 Invalid parameters:
- wrong number of registers 0x8004 Modbus server error Development environment Target system type PLC libraries to be linked TwinCAT v2.8.0 PC (i386) TcModbusSrv.Lib