beckhoff TS6250 — 7.1.11.7 FB_MBUdpWriteCoils (Modbus function 15)

PLC libraries This function is used for writing 1 to 2048 digital outputs (coils). One digital output corresponds to one bit of the write data bytes. VAR_INPUT VAR_INPUT sIPAddr : STRING(15); nTCPPort : UINT:= MODBUS_TCP_PORT; nUnitID : BYTE:=16#FF; nQuantity : WORD; nMBAddr : WORD; cbLength : UDINT; pSrcAddr : UDINT; bExecute : BOOL; tTimeout : TIME; END_VAR sIPAddr : Is a string containing the IP address of the target device. nTCPPort : Port number of the target device. nUnitID : Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nQuantity : Number of digital outputs to be written (data bits). nQuantity must be > 0.

nMBAddr: Start address of the digital outputs to be written (bit offset). cbLength : Contains the max. byte size of the source buffer containing the data to be written. The minimum buffer byte size must be: (nQuantity + 7) / 8 . pSrcAddr : Contains the address of the source buffer containing the data to be written. The buffer can be a single variable, an array or a structure, whose address can be found with the ADR operator. bExecute : The function block is activated by a rising edge at this input. tTimeout : States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBUSY : BOOL; bError : BOOL; nErrId : UDINT; cbRead :

UDINT; END_VAR bBusy : When the function block is activated this output is set. It remains set until an acknowledgement is received. bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId : Supplies the ADS error number when the bError output is set. Requirements TS6250 45 Version: 1.2 Function specific ADS error code Possible reason 0x8001 Modbus function not implemented 0x8002 Invalid address or length 0x8003 Invalid parameters: - wrong number of registers 0x8004 Modbus server error Development environment Target system type PLC libraries to be linked TwinCAT v2.8.0 PC (i386) TcModbusSrv.Lib